2004 IECC (supplement to 2003 IECC)
Residential
Regulatory
Requirements
The
U-factor and solar heat gain coefficient (SHGC) of fenestration
products shall be determined in accordance with National Fenestration
Rating Council Standards NFRC 100 and NFRC 200 respectively by
an accredited, independent laboratory, then labeled and certified
by the manufacturer. Products not meeting these requirements shall
be assigned product values based on defaults values. The default
values typically do not give full credit for energy efficient
performance.
Air
leakage requirements are set at 0.3 cfm/sf for windows and sliding
doors (cubic feet per minute per square foot of window area) and
0.5 cfm/sf for swinging doors. Fenestration systems must be tested
in accordance with AAMA/WDMA 101/I.S.2.
Simplified Prescriptive
Requirements
The IECC made signifcant
changes to the 2003 IECC and published them as a supplement to
the 2003 IECC. Fenestration was directly affected by the
changes. The US Department of Energy was the primary force
behind the changes. Their goal was to simplifiy the 2003
IECC.
The 2004 changes include:
- Dramatically simplified climatic zones (only 8 including humidity
references)
- Maximum U factors & SHGC when using trade offs
- Simplified Component and Prescriptive fenestration compliance
(see below)
The new prescriptive
tables by climate zone is shown below:
(Table
402.1 in the 2004 IECC supplement)
| Climate
Zone |
Fenestration
U-Factor |
Fenestration
SHGC |
1 |
1.20 |
0.40 |
2 |
0.75 |
0.40 |
3 |
0.65 |
0.40 |
4 except
marine |
0.40 |
None |
5 to 8
& marine 4 |
0.35 |
None |
Click
here to see the corresponding climate map.
Total UA alternative
If the total building
thermal envelope UA (sum of U-factor times assembly area) is less
than or equal to the total UA resulting from using the U-factors
in Table 402.1.2 (see below, multiplied by the same assembly area
as in the proposed building), the building shall be considered
in compliance with Table 402.1 (above). The UA calculation shall
be done using a method consistent with the ASHRAE Handbook of
Fundamentals and shall include the thermal bridging effects of
framing materials. The SHGC requirements shall be met in addition
to UA compliance.
(Table
402.1.2 in 2004 IECC supplement)
Climate
Zone |
Fenestration
U-Factor |
Skylight
U Factor |
| 1 |
1.2 |
0.75 |
2 |
0.75 |
0.75 |
3 |
0.65 |
0.65 |
4 except
marine |
0.40 |
0.6 |
5 &
marine 4 |
0.35 |
0.6 |
6 |
0.35 |
0.6 |
7 &
8 |
0.35 |
0.6 |
Simulated Performance
Alternative
This method allows the
designer to model the building using prescriptive method compliant
components creating a "standard" design and an associated energy
budget. The designer then may model the building again trading
off components against one another as long as the proposed design's
energy budget is less than the standard design's energy budget.
Some of the fenestration limitations on this approach are:
- U-Factor < 0.4 in zones 4 to 8
- SHGC < 0.55 in zones 1 to 3
- Standard and proposed design interior shading factors must
be equal (0.7 summer, 0.85 winter)
Note, the 2004 IECC
performance analysis now uses energy cost,
not consumption, for comparison (similar
to ASHRAE's methods.) This means that electicity use is penalized
since it is an expensive fuel. For fenestration, this means
that SHGC may be more heavily credited in the design since a SHGC
reduction will result in reduced cooling cost which is electrically
driven. This fact may allow the designer to trade off against
other components more easily.
|