ASHRAE 90.1
– 99 (Energy Standard for Buildings Except Low-Rise Residential
Buildings)
Regulatory requirements:
All fenestration
performance criteria (U-factor, Solar Heat Gain Coefficient, Emissivity,
Visible Transmittance and Air Leakage) must be determined in accordance
with NFRC (National Fenestration Rating Council) standards as
follows:
- NFRC 100 Procedure for Determining Fenestration
Product U-factors
- NFRC 200 Procedure for Determining Fenestration
Product Solar Heat Gain Coefficient at Normal Incidence
- NFRC 300 Procedure for Determining Solar Optical
Properties of Simple Fenestration Products
- NFRC 400 Procedure for Determining Fenestration
Product Air Leakage
In addition,
ASHRAE 90.1-99 requires that all performance criteria
“shall be determined by a laboratory accredited by a nationally
recognized accredited organization, such as the National Fenestration
Rating Council and shall be labeled and certified by the manufacturer.”
Prescriptive
Requirements
The Prescriptive
Building Envelope Option recognizes the advances made in fenestration
performance over the last ten years by allowing vertical fenestration
area up to 50% of the gross wall area. If a building
has greater than 50% glazing area (or greater than 5% fenestration
area in the roof) another compliance path must be used (i.e.,
the Trade-Off Option, Energy Cost Budget Method).
The prescriptive
option has maximum requirements for U-factor and Solar Heat Gain
Coefficient. These requirements are based on local climate (heating
and cooling degree days) and building orientation. Fenestration
U-factors requirements range from 0.29 to 1.27, while SHGC requirements
range from 0.14 to no requirement. In addition, the standard provides
a credit for overhangs that provide shading.
Air leakage
shall not exceed 1.0 cfm/ft 2 (cubic feet per minute per square
foot of door area) for glazed winging entrance doors and 0.4 cfm/ft
2 for all other products (note that field glazed products are
exempt from these air leakage requirements).
The
Building Envelope Trade-Off Option
ASHRAE
90.1-99 provides a trade-off option to assist in compliance. This
option allows the performance of one envelope component to be
improved to make-up for another component that does not meet minimum
requirement (note that this option cannot be used to trade-off
between the building envelope and the lighting or mechanical system).
When using the trade-off option, the visible transmittance
of the fenestration systems must also be specified. This
is used for determining the potential for daylighting.
Software
is available of for calculating these trade-offs. The “ENVSTD”
program meets all the Building Envelope Trade-Off Option requirements.
ASHRAE publishes a user's manual and the ENVSTD software.
System
or Design Requirements
The system
or design requirements are in ASHRAE 90.1 and outlined in the
Energy Cost Budget Method. It is used to evaluate the compliance
of proposed building designs and is intended for use with simulation
programs that model building efficiency (ENVSTD). The models must
report energy usage by lights, internal equipment loads, and service
water heating equipment, space cooling and heat rejection equipment,
fans and other HVAC equipment. Using this approach, architects,
builders, and designers can increase the use of glass in buildings
by specifying high performance glass products (i.e., spectrally
selective tinted and coated glass) to control solar heat gain
and take advantage of lighting energy savings from daylighting.
.
|